NHP DSRCBH1030A RCBO Din Safe - 1P - 10A - 30MA - 10KA

  • NHP
  • BW#: 08579873
  • Mfr#: DSRCBH1030A
  • UNSPSC#: 39121601
Login or Register to view price
QTY

Features
  • High speed and rapid arc quenching technology ensuring the highest level of protection is provided


  • Specifications

  • Service Information: Product is not repairable
  • Standards Compliance: IEC 60077-16-3, IEC 60068-2-6, UL 94 V-2, IEC 60068-2, DIN 40046, IEC 60947-1
  • Certifications: CE, RCM
  • Add-On Devices (side add-on): Panelboard Switch
  • Component Type Power Distribution & Protection: RCBO
  • Number of Poles versus Modules: 1
  • Approval(s): N17482
  • Busbar System, Bottom: Fork, Pin
  • Selectivity Class (IEC 60898): A
  • Icn, Rated Short-Circuit Capacity, 1P, 230/400V AC: 10 kA
  • Im, Rated Make/Break Capacity: 100 A
  • In, Rated Current at 30°C: 10 A @30°C
  • Icn, Rated Short Circuit Capacity: 10 kA
  • Inc, Rated Conditional Short Circuit Current: 10 kA
  • Depth: 76 mm
  • Dielectric Strength: 2500V V AC
  • Rated Frequency: 50/60 Hz
  • Height: 125 mm
  • Relative Humidity, Max: 95 %RH
  • IP Rating, Inside: IP40
  • IP Rating, Outside: IP20
  • Mounting: DIN-35 Rail Mount
  • Package Quantity: 1 qty
  • Padlockable: Yes, Captive and Non-Captive (Ordered Separately)
  • Poles: 1P + N
  • Conductor Entry Position: Bottom
  • Flammability Rating (UL94): UL 94 V-2
  • Shock Rating: IEC 60077-16-3
  • Vibration Rating: IEC 60068-2-6
  • Insulation Resistance: 1000 MΩ
  • Electrical Service Life at Un, In: 10000 cycles
  • Mechanical Service Life: 20000 cycles
  • Shock Acceleration (Max.): 40 g
  • Shock Duration (Max.): 5 ms
  • Operating Temperature, Max: 55 °C max
  • Operating Temperature, Min: -5 °C min
  • Storage Temperature, Max: 70 °C max
  • Storage Temperature, Min: -25 °C min
  • Tightening Torque, Bottom, Nominal: 4.5 Nm
  • Tightening Torque, Top, Nominal: 3 Nm
  • Trip Curve: C
  • RCD Type, AS/NZS 61008/61009: A
  • Vibration Acceleration (Max.): 2 m/s²
  • Vibration Duration (Max.): 30 min
  • Vibration Frequency, Operational (Max.): 80 Hz
  • Uimp, Impulse Withstand Voltage, 1.2/50µs: 6 kV, 1.2/50µs
  • Impulse Withstand Test Voltage: 6 kV
  • Ui, Rated Insulation Voltage: 500 V (rms)
  • Un, Nominal Operational Voltage, AC: 240 V AC
  • Ubmax, Service Voltage, AC, Max: 265 V AC
  • Ubmin, Service Voltage, AC, Min: 195 V AC
  • Weight: 0.35 kg
  • Width: 18 mm
  • Wire/Conductor Size, Flex Cable, Bottom, Max: 25 mm² Bottom
  • Wire/Conductor Size, Flex Cable, In, Min: 1 mm² In
  • Wire/Conductor Size, Flex Cable, Out, Min: 1 mm² Out
  • Wire/Conductor Size, Flex Cable, Top, Max: 16 mm² Top
  • Wire/Conductor Size, Rigid Cable, Bottom, Max: 35 mm² Bottom
  • Wire/Conductor Size, Rigid Cable, In, Min: 1 mm² In
  • Wire/Conductor Size, Rigid Cable, Out, Min: 1 mm² Out
  • Wire/Conductor Size, Rigid Cable, Top, Max: 25 mm² Top
  • Isolator Application, IEC 60947-2: Yes
  • Neutral Pole Protected: No. Sealable: Yes
  • Trip-Free Mechanism: Yes
  • Centre Trip Position: No. Neutral Pole Switched: No. IΔc, Rated Conditional Residual Short-Circuit Current: 10000 A
  • IΔc, Rated Conditional Residual Short-Circuit Current: 10 kA
  • IΔm, Rated Residual Make/Break Capacity: 10000 A
  • IΔn, Rated Leakage Current: 30 mA
  • Tripping Time at IΔn, Instantaneous: <40 ms
  • Minimum sell quantity:

    Order Quantity Multiple:

    Technical Specifications

    Number of Pole 1P + N
    Type RCBO
    Current Rating 10 A @30°C
    Width 18 mm
    Depth 70 mm
    Tripping Curve C
    Height 125 mm
    Rated Impulse Withstand Volt 6 kV, 1.2/50µs
    Rated Insulation Voltage 500 V (rms)
    Mounting Mode DIN-35 Rail Mount